You are using an outdated browser version not supported by this website.
Click here to upgrade your browser
5,288 products with technical literature, drawings and more from leading suppliers of NZ architectural materials.
Case studies, new products and product news from leading suppliers of NZ architectural materials.
Blogs for architectural specifiers, offering product, design and business advice.
Flush Box Intumescent Pads are designed to be installed into metal flush boxes installed in hollow fire rated walls.
All tests conducted in accordance with AS1530.4 - 2005 and AS4072.1 - 2005.
As per requirements set out in NZBC C/AS2 Clause 4.4 Allproof fire stopping products installation “shall be identical to those of the prototype used in tests to establish their FRR”.
Allproof passive fire systems are required to be used in closed, internal spaces, protected from excessive moisture, solvents, oxidising agents, acids and alkalis. They should not be exposed to UV light in service.
Separation or protection must be provided to Allproof Passive Fire Protection Products from heat sources such as fireplaces, heating appliances and chimneys. Part 7 of NZBC Acceptable Solution C/AS1 and C/AS2, and NZBC Verification Method C/VM1 provide methods for separation and protection of combustible materials from heat sources.
NZBC C/AS2 C3.1, C3.2 and C3.3: Allproof PFP products are designed to limit the spread of fire between property from its origin by sealing service penetrations in the separating elements of fire cells. The Technical Literature gives the fire resistance ratings (FRRs) for the Allproof Passive Fire Protection Products that can be achieved to provide the FRR’s as determined by NZBC Acceptable
Solutions C/AS1, C/AS2 and NZBC Verification Method C/VM2.
NZBC C/AS2 4.4 Fire Stopping: Allproof PFP products have been tested in accordance with Appendix C C5.1 for fire stopping. Detailed information on the tested prototypes is available in Allproof’s PFP literature to assist with the correct product selection and install details. When installed as per documentation Allproof PFP products will provide an FRR consistent with the published results and therefore, if selected correctly, no less than the separating element.
NZBC B2: Allproof Passive Fire Protection Products meet code compliance with the NZBC Clause B2.3.1 (b), 15 years.
NZBC F2.3.1 Allproof Passive Fire Protection Products does not present a health hazard to people
These products have been used in a huge variety of buildings including government and council projects such as schools.
At the core of the Allproof passive fire protection product range is the advanced intumescent technology. This enables Allproof to offer products with performance and design advantages for engineers and installers of passive fire protection products.
Allproof's intumescent material expands when exposed to heat and as its volume increases with significant expansion pressure, it produces a stable char. The intumescent char formed is a poor conductor of heat, retarding heat transfer and retaining the integrity and insulation of service penetrations through otherwise fire-resistance rated walls or floors.
A New Zealand owned company specialising in the manufacture of plumbing and drainage products and systems.
Product EnquiriesNew and updated architectural products, design solutions, inspiration, technical advice and more when you sign up for EBOSS.